11 Supplement
VEGAFLEX 83 • Modbus and Levelmaster protocol
41838-EN-130314
Set Receive to Transmit Delay
Request:
Parameter Length Code/Data
Set Receive to Transmit Delay 7 characters ASCII UuuRmmm
mmm = milliseconds (50 up to 250),
default = 127 ms
Response:
Parameter Length Code/Data
Set Receive to Transmit Delay 6 characters ASCII UuuROK
Report Number of Floats
Request:
Parameter Length Code/Data
Set Receive to Transmit Delay 4 characters ASCII UuuF
Response:
Parameter Length Code/Data
Set Receive to Transmit Delay 5 characters ASCII UuuFn
n = number of measurement values
(0, 1 or 2)
Report Receive to Transmit Delay
Request:
Parameter Length Code/Data
Report Receive to Transmit Delay 4 characters ASCII UuuR
Response:
Parameter Length Code/Data
Report Receive to Transmit Delay 7 characters ASCII UuuRmmm
mmm = milliseconds (50 up to 250),
default = 127 ms
Error codes
Error Code Name
EE-Error Error While Storing Data in EEPROM
FR-Error Erorr in Frame (too short, too long, wrong data)
LV-Error Value out of limits