79
11 Supplement
VEGAFLEX 83 • Modbus and Levelmaster protocol
41838-EN-130314
Request:
Parameter Length Code/Data
Function Code 1 Byte 0x08
Sub Function Code 2 Bytes
Data N*2 Bytes Data
Response:
Parameter Length Code/Data
Function Code 1 Byte 0x08
Sub Function Code 2 Bytes
Data N*2 Bytes Data
Implemented function codes:
Sub Function Code Name
0x00 Return Data Request
0x0B Return Message Counter
With sub function codes 0x00 only one 16 bit value can be written.
FC16 Write Multiple Register
With this function code, several holding registers can be writen. Only registers can be written in an
enquiry which are immediately consecutive. If there are gaps (registers do not exist) between the
registers, then they cannot be written in a telegram.
Request:
Parameter Length Code/Data
Function Code 1 Byte 0x10
Start Address 2 Bytes 0x0000 to 0xFFFF
Register Value 2 Bytes 0x0001 to 0x007B
Byte Number 1 Byte 2*N
Register Value N*2 Bytes Data
Response:
Parameter Length Code/Data
Function Code 1 Byte 0x10
Sub Function Code 2 Bytes 0x0000 to 0xFFFF
Data 2 Bytes 0x01 to 0x7B
FC17 Report Slave ID
With this function code, the Slave ID can be queried.
Request:
Parameter Length Code/Data
Function Code 1 Byte 0x11