71
11 Supplement
VEGAFLEX 83 • Modbus and Levelmaster protocol
41838-EN-130314
Gas phase Temperature Pressure
1 bar (14.5 psig) 10 bar (145 psig) 50 bar (725 psig)
Steam (saturated
steam)
100 °C/212 °F 0.26 % - -
180 °C/356 °F 0.17 % 2.1 % -
264 °C/507 °F 0.12 % 1.44 % 9.2 %
366 °C/691 °F 0.07 % 1.01 % 5.7 %
Characteristics and performance data
Measuring cycle time
< 500 ms
Step response time
4)
≤ 3 s
Max. lling/emptying speed 1 m/min
Ambient conditions
Ambient, storage and transport tempera-
ture
-40 … +80 °C (-40 … +176 °F)
Process conditions
For the process conditions, please also note the specications on the type label. The lowest value
always applies.
The measurement error from the process conditions is in the specied pressure and temperature
range of below 1 %.
Process pressure -1 … +16 bar/-100 … +1600 kPa (-14.5 … +232 psig),
depending on the process tting
Vessel pressure relating to the ange
nominal stage
see supplementary instructions manual "Flanges ac-
cording to DIN-EN-ASME-JIS"
Process temperature (thread or ange temperature)
Ʋ FKM (SHS FPM 70C3 GLT) -40 … +150 °C (-40 … +302 °F)
Ʋ EPDM (A+P 75.5/KW75F) -40 … +150 °C (-40 … +302 °F)
4)
Time span after a sudden measuring distance change by max. 0.5 m in liquid applications, max 2 m with bulk
solids applications, until the output signal has taken for the rst time 90 % of the nal value (IEC 61298-2).