Quick start
VEGAFLEX 83 • Modbus and Levelmaster protocol
41838-EN-130314
1. In this menu item you can select the application. You can choose
between level and interface measurement.
2. In the menu item "Medium - Dielectric constant" you can dene
the medium type (medium).
3. Carry out the adjustment in the menu items "Min. adjustment" and
"Max. adjustment".
4. A "Linearization" is required for all vessels in which the vessel vol-
ume does not increase linearly with the level - e.g. in a horizontal
cylindrical or spherical tank. Activate the appropriate curve.
5. A "False signal suppression" detects, marks and saves the false
signals so that they are no longer taken into account for level
measurement. We generally recommend a false signal suppres-
sion.
The sensor measures the distance from the sensor (reference plane)
to the product surface.
2
4
5
3
1
2
4
5
3
1
Fig. 3: Measuring ranges - VEGAFLEX 83
1 Reference plane
2 Probe length L
3 Measuringrange(defaultsettingreferstothemeasuringrangeinwater)
4 Upperdeadband(inthisareanomeasurementispossible)
5 Lowerdeadband(inthisareanomeasurementispossible)
For this adjustment, the distance is entered when the vessel is full
and nearly empty. If these values are not known, an adjustment with
other distances, for example, 10 % and 90 % is also possible. Starting
point for these distance specications is always the seal surface of
the process tting.
Parameterization example