6 Set up with the display and adjustment module
VEGAFLEX 83 • Modbus and Levelmaster protocol
41838-EN-130314
Menu Menu item Default value
Setup Block operation Released
Measurement
loop name
Sensor
Units Distance unit: mm
Temperature unit: °C
Probe length Length of the probe Ex factory
Product type Liquid
Application Level, vessel
Medium, dielectric
constant
Water-based, > 10
Max. adjustment 0.000 m(d) - note blocking distances
Min. adjustment Probe length - take dead band into
account
Linearization Linear
Damping
0.0 s
Scaling size Volume in l
Current output,
adjustment
0.00 lin %, 0 l
100.00 lin %, 100 l
Current output
mode
Last measured value
Current output
Min./Max.
Min. current 3.8 mA, max. current
20.5 mA
Display Language As set in the device
Displayed value 1 Filling height Level
Displayed value 2 Electronics temperature
Backlight Switched o
Additional settings PIN 0000
Probe type Like order
HART mode Address 0 - Analogue current output
with HART
The instrument settings are copied with this function. The following
functions are available:
Read from sensor: Read data from sensor and store into the
display and adjustment module
Write into sensor: Store data from the display and adjustment
module back to the sensor
The following data or settings for adjustment of the display and ad-
justment module are saved:
All data of the menu "Setup" and "Display"
In the menu "Additional adjustments" the items "Reset, Date/Time"
Special parameters
Additional adjustments -
Copy instrument settings