Quick start
VEGAFLEX 83 • Modbus and Levelmaster protocol
41838-EN-130314
Quick start
The quick start procedure enables a quick setup with many applica-
tions. You can nd further information in the respective chapters of the
operating instructions manual.
1. Distance from the metallic vessel wall > 300 mm. Distance from
non-metallic vessel wall > 500 mm. The probe must not touch any
installations or the vessel wall.
2. Place a metal sheet beneath the process tting with non-metal
vessels.
1 2
Fig. 1: Installation in plastic silo
1 Flange
2 Metal sheet
3. If necessary, fasten probe end.
For further information see chapter "Mounting".
1. Make sure that the power supply corresponds to the specica-
tions on the type label.
2. Connect the instrument according to the following illustration
+
+
power supply
MODBUS
D0
D1
IS GND
USB
1
2
1345
2off
on
( )
(
)
(-)
(-)
Fig. 2: Connection compartment
1 USB connection
2 Slideswitchforintegratedterminationresistor(120Ω)
For further information see chapter "Connecting to power supply".
For standard applications we recommend selecting the "Quick setup"
in the display and adjustment module.
Mounting
Electrical connection
Set parameters