Vega VEGAFLEX 83 Modbus and Levelmaster protocol PFA in Manual de usuario Pagina 85

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 100
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 84
85
11 Anexo
VEGAFLEX 83 • Protocolo Modbus y Levelmaster
41838-ES-130416
SetReceivetoTransmitDelay
Request:
Parámetro Length Code/Data
Set Receive to Transmit Delay 7 characters ASCII UuuRmmm
mmm = milliseconds (50 up to 250),
default = 127 ms
Response:
Parámetro Length Code/Data
Set Receive to Transmit Delay 6 characters ASCII UuuROK
Report Number of Floats
Request:
Parámetro Length Code/Data
Set Receive to Transmit Delay 4 characters ASCII UuuF
Response:
Parámetro Length Code/Data
Set Receive to Transmit Delay 5 characters ASCII UuuFn
n = number of measurement values
(0, 1 or 2)
ReportReceivetoTransmitDelay
Request:
Parámetro Length Code/Data
Report Receive to Transmit Delay 4 characters ASCII UuuR
Response:
Parámetro Length Code/Data
Report Receive to Transmit Delay 7 characters ASCII UuuRmmm
mmm = milliseconds (50 up to 250),
default = 127 ms
Código de error
Error Code Name
EE-Error
ErrorWhileStoringDatainEEPROM
FR-Error Erorr in Frame (too short, too long, wrong data)
LV-Error Value out of limits